Thanks!  I have an e-mail archive that goes back to when Doug originally 
set up this EV Gray Group.

On 11/20/2018 1:57 PM, James Glinski [email protected] [EVGRAY] wrote:
>
> Norm good article  you might just copy and file it away with a short 
> cut link so when some one needs a refresher it's just a click away for 
> you .Yahoo isn't workable for many. Of us and this will disappear like 
> the dew on the grass when the sun comes up  . it's a little to good to 
> have It vanish .away . thinks for your input your appreciated .
>
> On Tuesday, November 20, 2018, Mick [email protected] 
> <mailto:[email protected]> [EVGRAY] <[email protected] 
> <mailto:[email protected]>> wrote:
>
>     Norm,
>
>     Thank you for the in depth post of your experience uncovering this
>     event.  Sorry to frustrate you with what seem like repetitive
>     questions. Everything here is understood.  My question had to do
>     with the source side of the whole systemic occurrence and not that
>     I don't understand just that I like things to be very succinct in
>     my small brain, therefore I was trying to map out the circuit
>     including all E and B field connections in order that for instance
>     the ceiling fan experiment be replicated from a battery inverter
>     source without connection to the utility.  In other words the DUH
>     I brought up the other week.  You have explained the phenomenon
>     and it's creation many times but seem to have left out the
>     functions from the source side of the circuit and how that
>     interacts with the whole experiment and magnetic
>     connect-anniliation-reconnect.
>
>     I have successfully replicated the shots to larger and smaller
>     scale while using the utility sourced power but not yet reliably
>     from an inverter driven isolated system so attempting to determine
>     the best way to move forward on the source side without burning up
>     any more devices or at least a minimum so.  I think I need to
>     procure an iso transformer with a center tap and ground it on the
>     sink side to the center tap in order there is the magnetic
>     connection to the earth on source side in the first place not just
>     the ground rod on the sink side of the experiment.  Otherwise part
>     two will require a giant stepdown of similar proportions to a pole
>     pig.  Just trying to streamline and keep expenses low.
>
>     I hope the above does not further frustrate you but rather conveys
>     the why of my question which I can see seemed to be circular and
>     puerile. Sorry to offend.
>
>     By the way I don't know if you had posted this story before but
>     with Yahoo and search and all your references to the neutral spike
>     event I have never uncovered it.
>
>     Thank again!
>
>     On 11/20/2018 6:58 AM, Norman Wootan [email protected]
>     <mailto:[email protected]> [EVGRAY] wrote:
>>
>>     Mick!  I am getting just like Hector here by having to explain
>>     something over and over!  I guess short memory is the cause for
>>     lack of understanding the whole project. First you have to go
>>     back to the 1981 ceiling fan, 1/6th HP capacitor run shaded pole
>>     motor problem. A wiring error by a Chinese assembly worker
>>     incorrectly wired the capacitor reversing switch into the neutral
>>     side of the circuit which provided a total isolation of charge
>>     while the switch was in transition from forward operation  to
>>     reverse operation. Reversing switch would explode.  This was my
>>     first encounter with the phenomenon which I researched and
>>     determined that it was a Magneto-Electric effect or better put,
>>     Magnetic flux annihilation-reconnect as we now know it. In
>>     Physics we have always been taught that energy cannot be
>>     destroyed but can change forms as we clearly see by simple
>>     experiment. With this knowledge tucked back in the memory bank, I
>>     had the occasion to encounter this phenomenon again in around
>>     1984. A wealthy widow had remodeled her expansive Highland Park
>>     home (Dallas) and I had installed a projection TV system into her
>>     den.   MS. Sharp called and said  she had a Poltergeist in her
>>     den. When I arrived she served tea and told me to sit there and
>>     wait a few minutes.  The TV screen and projector both started
>>     descending from the ceiling then reversed and went back up. Both
>>     these motors were shaded pole, capacitor run design so that
>>     switching via wall switch could reverse operation, either up or
>>     down against limit switches. Here is the Somfy motor example so
>>     you understand how they operate:
>>     https://www.youtube.com/watch?v=EMHEJ2iIu14&feature=youtu.be
>>     <https://www.youtube.com/watch?v=EMHEJ2iIu14&feature=youtu.be>
>>     When I went into attic to examine the motorized units the
>>     phenomenon occurred again. Sure enough the screen and projector
>>     descended half way down then reversed and retracted. Over my head
>>     was a powered turbo ventilator attic fan of shaded pole design
>>     which took off ZIIIIINNNNG , super fast acceleration up to a
>>     speed about 10X design speed but one big problem was that it took
>>     off backwards! The turbine took several minutes to coast down to
>>     a stop.  A visit downstairs found that a small appliance like a
>>     counter top blender in the kitchen (shaded pole motor) would take
>>     off spinning backwards then stop.  The only connection that all
>>     these motor had when sitting in a turned off state was a
>>     connection to the neutral buss.   Interesting fact was that with
>>     the very small size motor windings and sudden fantastic
>>     acceleration up to very high speed (backwards) did no damage to
>>     the motors. I did an inspection to the mains breakers and house
>>     wiring including the service cabelling and earth ground at the
>>     mains panel. All was up to Dallas Code. While walking in side
>>     yard, I found a brand new installation of a 5 ton A/C Condensing
>>     unit. in addition to the older 5 ton unit. Both units were earth
>>     bonded via the Required (Highland Park Code) 10 ft. ground rod at
>>     the units.  Both units were 5  Ton, 230VAC single phase.   While
>>     I was looking at the A/C units , the new one tried to start
>>     against a locked rotor condition. From contactor closure to
>>     WHUUUUUMP, EMP shot which you could feel the brissance in the
>>     ground took about 1/2 second.  This was the source of the EMP
>>     event which caused the neutral buss to carry this very unusual
>>     form of energy.  The A/C guys came out and replaced the
>>     compressor and rectified the situation but I came away with a
>>     better understanding a very common phenomenon that most do not
>>     take time to fully understand nor appreciate the implications.  
>>     By studing the ongoing research of the natural occurrence of this
>>     EMP phenomenon from Solar magnetic storms Magnetic Annihilation
>>     -Reconnect which have been duplicated in Labs gathering better
>>     understanding of phenomenon. I elected to bench top duplicate the
>>     situation which I had observed back in 1984 at the Sharp
>>     residence.  Since I was doing HVAC, Electrical and Electronics
>>     Contracting, I had many compressors at my disposal just like the
>>     one in the Carrier A/C unit.    By hydraulic locking the
>>     compressor via filling with oil and pinching off the suction and
>>     discharge lines you have a fully locked up sealed unit See:
>>
>>     This unit utilizes a 40mfd start cap and a 5mfd run cap
>>     controlled by current relay. When energized via 2 pole,230VAC,
>>     starter contactor, both the start and run windings are energized.
>>     When the Over current relay senses the locked rotor current of 84
>>     amps ( motor in magnetic saturation) the circuit is opened
>>     leaving the stored energy in total isolation with no ground
>>     reference.  A NECESSARY CONDITION TO GET THE MAGNETIC FLUX
>>     ANNIHILATION-Re-CONNECT PHENOMENON or EMP.     This experiment is
>>     something anyone can duplicate and observe the phenomenon for
>>     yourself.  The reversible ceiling fan is the simplest and easiest
>>     and less expensive to replicate. Most current available
>>     reversible fans utilize the electrical capacitor relocation via
>>     toggle switch to reverse rotation.  All you have to do is open up
>>     circuit and re-wire the cap so that you have a momentary loss of
>>     ground reference (neutral) while the reversing switch is in
>>     transit. Reverse it several times and you will explode switch!  
>>     Now Mick, what do you not understand??   I was just too curious
>>     to let this go by without finding an answer. Just remember the
>>     Axiom, Energy cannot be destroyed but it can change forms.
>>
>>     On 11/19/2018 10:04 AM, Mick [email protected]
>>     <mailto:[email protected]> [EVGRAY] wrote:
>>>
>>>     Norm,
>>>
>>>     So why did you first notice this even at a clients, shorted
>>>     start cap or seized bearing?     Interesting I have noticed a
>>>     ground rod near pool equipment with GFI but rarely have seen or
>>>     can recall one next to a heat pump or AC unit and 10 feet ground
>>>     rod damn that's deeper than a dirt nap.  At 60hz the capacitive
>>>     coupling is negligible.
>>>
>>>     Unless I am misunderstanding something the L1-L2 at the supply
>>>     side... coupling to earth would still be at the transformer to
>>>     center tap neutral back at the pole then the neutral is ground
>>>     bonded at the service.  Since it is on the sink side of the
>>>     transformer from the utility there is a direct path to ground
>>>     through a certain impedance,reactance and reluctance whatever
>>>     importance that plays into the event.
>>>
>>>     On 11/19/2018 4:44 AM, Norman Wootan [email protected]
>>>     <mailto:[email protected]> [EVGRAY] wrote:
>>>>
>>>>     Locked means exactly what the term expresses! No rotor motion
>>>>     relative to stator!  On the early 5 Ton A/C units they were
>>>>     service wired with a 3 conductor wip from service disconnect to
>>>>     A/C unit! You had L-1 & L-2 230VAC (hots) and a green earth
>>>>     bonding wire to motor and chasis frame. In addition, you had
>>>>     a10 ft. ground stake into earth ground to bond this outdoor
>>>>     installation for safety reasons. When over-current relay (84
>>>>     amps) drops out starter contactor there is NO GROUND PATH to
>>>>     discipate the charge, both magbetic flux sayuration (Inductive
>>>>     power) and the two charged capacitors in the circuit.  This
>>>>     energy is in an isolated state due to insulation in the motor
>>>>     windings and capacitors. Ole will jump in here and say there is
>>>>     capacitive coupling between motor frame and isolated
>>>>     capacitance and magnetic flux at saturation.    I built and did
>>>>     the test on this phenomenon after I saw it in real life in a
>>>>     clients back yard.  Easy to duplicate!  The reversible ceiling
>>>>     fan trick can be done by anyone by just changing the wiring on
>>>>     the reversing capacitor in-order to float neutral while the
>>>>     reversing switch is in transition.  Simple! ( BOOM)!!
>>>>
>>>>     On 11/18/2018 11:15 AM, Mick [email protected]
>>>>     <mailto:[email protected]> [EVGRAY] wrote:
>>>>>
>>>>>     Norm,
>>>>>
>>>>>     How did you run the motor in locked mode, by preventing the
>>>>>     start cap from energizing?
>>>>>
>>>>>     When you experimented with the energy from this motor where
>>>>>     did you extract the differential, from the green wire running
>>>>>     back to the service panel or another grounding rod and from
>>>>>     the motor frame where the ground bonding clip usually is or
>>>>>     somewhere else?
>>>>>
>>>>>     Assuming frame on your dual winding induction motor was
>>>>>     isolated sink side from the stator windings by their
>>>>>     insulation  as you mentioned earlier there was no neutral and
>>>>>     on the source side by the center tap in the pole pig?
>>>>>
>>>>>     Not sure why I was thinking locked was synchronous mode as we
>>>>>     discussed earlier the concept of Mag Transmitter is to
>>>>>     saturate the core and release, or as Hector likes to say
>>>>>     switch off to turn on.  Some major issues going on here, head
>>>>>     on backwards.
>>>>>
>>>>>     So impedance does opposite of a LC tank and dropped like a
>>>>>     series LC hmmm...
>>>>>
>>>>>     Thanks,
>>>>>
>>>>>     Mick
>>>>>
>>>>>
>>>>>     On 11/18/2018 3:44 AM, Norman Wootan [email protected]
>>>>>     <mailto:[email protected]> [EVGRAY] wrote:
>>>>>>
>>>>>>     Thanks! Ole for the explanation!  Rotation is required
>>>>>>     inorder for counter emf to be generated. In stalled rotor or
>>>>>>     locked rotor conditions, the current through the windings is
>>>>>>     only limited by R = resitance. My dual winding 5 HP motor in
>>>>>>     locked rotor had a combined current draw of 84 amps @ 230VAC
>>>>>>     input. When you look at the BH curve on a scope you see the
>>>>>>     magnetic flux build to saturation at which point the
>>>>>>     impedance is = to Zero ( air value) with R being the only
>>>>>>     limiting factor. (Ole). I used the dual winding motor for it
>>>>>>     has a starting cap value of 40mfd and a run cap with a value
>>>>>>     of 5 mfd, both of which are in circuit when current limiting
>>>>>>     relay drops circuit open yielding the Neutral Spike form
>>>>>>     ground. Magneto Electric effect. For it to work, the caps and
>>>>>>     motor windings have to be isolated from neutral and earth
>>>>>>     ground reference.  the iron motor frame is earth bonded.
>>>>>>     Cancellation of energy in isolation will create an EMP earth
>>>>>>     ground response.  This goes back to Page 25 of CSN by Tesla
>>>>>>     himself.
>>>>>>
>>>>>>     On 11/17/2018 5:12 PM, [email protected]
>>>>>>     <mailto:[email protected]> [EVGRAY] wrote:
>>>>>>>
>>>>>>>     Locked rotor is when the rotor is prevented from rotating.
>>>>>>>     This is also known as stalled rotor.
>>>>>>>
>>>>>>>     Synchronous speed is when the rotor follows the rotating
>>>>>>>     magnetic wave(s) of the stator. In an induction motor
>>>>>>>     (asynchronous motor) this means no power transmission
>>>>>>>     between the rotor and the stator. The motor is then working
>>>>>>>     neither as motor or generator.
>>>>>>>
>>>>>>>     Slip is the ratio between the rotor speed and the rotating
>>>>>>>     field speed.
>>>>>>>
>>>>>>>     Regards
>>>>>>>     Ole
>>>>>>>
>>>>>>>
>>>>>>>     ---In [email protected]
>>>>>>>     <mailto:[email protected]>, <mkjekyll@...>
>>>>>>>     <mailto:mkjekyll@...> wrote :
>>>>>>>
>>>>>>>     Norm,
>>>>>>>
>>>>>>>     I am slowly digesting this but I think my concept of locked
>>>>>>>     rotor was/is in error.  Always thought this was when the
>>>>>>>     rotor is locked to the rotational field from stator with
>>>>>>>     least amount of slip, seems like I am reading now it is most
>>>>>>>     amount of slip.
>>>>>>>
>>>>>>>     Can you provide what locked rotor means to you and any
>>>>>>>     additional information of what you think may be occurring
>>>>>>>     beyond the everyday accepted definition?
>>>>>>>
>>>>>>>     Thanks,
>>>>>>>
>>>>>>>     Mick
>>>>>>>
>>>>>>>     On 11/16/2018 5:55 AM, Norman Wootan nwootan@...
>>>>>>>     <mailto:nwootan@...> [EVGRAY] wrote:
>>>>>>>
>>>>>>>>         Mick, Ole, Kone etal!  I have been thinking a lot about
>>>>>>>>         my Locked Rotor experiments and did a lot of reading to
>>>>>>>>         come up with a fool proof Lenz free motor / generator
>>>>>>>>         combination which is so easy to build and proof test!
>>>>>>>>         First of all you should read what we know as facts! See
>>>>>>>>         the following articles:
>>>>>>>>
>>>>>>>>         https://www.motioncontroltips.com/faq-what-are-dc-shunt-motors-and-where-are-they-used/
>>>>>>>>         <https://www.motioncontroltips.com/faq-what-are-dc-shunt-motors-and-where-are-they-used/>
>>>>>>>>
>>>>>>>>         http://www.machineryspaces.com/direct-current-motors.html
>>>>>>>>         <http://www.machineryspaces.com/direct-current-motors.html>
>>>>>>>>
>>>>>>>>         https://www.quora.com/What-will-happen-if-the-back-EMF-of-a-DC-motor-vanishes
>>>>>>>>         <https://www.quora.com/What-will-happen-if-the-back-EMF-of-a-DC-motor-vanishes>
>>>>>>>>
>>>>>>>>         https://www.youtube.com/watch?v=3-FPcKgwSzs&feature=youtu.be
>>>>>>>>         <https://www.youtube.com/watch?v=3-FPcKgwSzs&feature=youtu.be>
>>>>>>>>
>>>>>>>>         https://www.youtube.com/watch?v=x3TFALmHtMw&feature=youtu.be
>>>>>>>>         <https://www.youtube.com/watch?v=x3TFALmHtMw&feature=youtu.be>
>>>>>>>>
>>>>>>>>         https://www.researchgate.net/post/A_DC_shunt_motor_is_running_at_light_load_what_happens_if_the_field_winding_gets_opened
>>>>>>>>         <https://www.researchgate.net/post/A_DC_shunt_motor_is_running_at_light_load_what_happens_if_the_field_winding_gets_opened>
>>>>>>>>
>>>>>>>>         Kone loves to play with the very powerful Neos as found
>>>>>>>>         at K&G Magnetics and shown in the video of the Ray's
>>>>>>>>         LENZ free generator. What I will propose is very simple
>>>>>>>>         application of DC motor principles as read from the
>>>>>>>>         cited references. First you make your LENZ free  motor
>>>>>>>>         which is in reality a LINEAR MOTOR (Solenoid) which
>>>>>>>>         will give the necessary stroke length to drive the
>>>>>>>>         LINEAR generator (Coil oscillating within the drag
>>>>>>>>         free, LENZ free area of the Neo magnets). Stroke of the
>>>>>>>>         solenoid is controlled by Hall sensor and IGBT drive
>>>>>>>>         switch to give an excursion rate (stroke) at a
>>>>>>>>         frequency of 60 HZ. By using a DC pulse  to drive the
>>>>>>>>         solenoid coil it is tricked into being in LOCKED ROTOR
>>>>>>>>         condition, thus no LENZ effect.  Has the light come on
>>>>>>>>         yet??   We know that Ray's generator puts out a sine
>>>>>>>>         wave output (AC) with no LENZ drag. Following the DC
>>>>>>>>         motor principles as applied to the solenoid driver, you
>>>>>>>>         have a motor that is LENZ free also. The combo should
>>>>>>>>         give an Over-unity output. Now the tricky part!  We
>>>>>>>>         know as Ole will agree in that when you switch the
>>>>>>>>         solenoid power to off state as magnetic flux is
>>>>>>>>         building toward saturation there will be a huge voltage
>>>>>>>>         spike (Neutral Spike) which we have to capture and not
>>>>>>>>         send to ground as ordinary practice in solid state
>>>>>>>>         switch design (snubber diodes)  The capture of the
>>>>>>>>         SPIKE energy (HV) which occurs naturally will be the
>>>>>>>>         over-unity factor here! Interesting concept! Think
>>>>>>>>         about it!  Norm Mick! (accumulator HV caps)!
>>>>>>>>
>>>>>>>>         On 11/16/2018 6:23 AM, Mick mkjekyll@...
>>>>>>>>         <mailto:mkjekyll@...> [EVGRAY] wrote:
>>>>>>>>>
>>>>>>>>>         Ole,
>>>>>>>>>
>>>>>>>>>         I have had caps charge much faster in an LC tank than
>>>>>>>>>         otherwise, but it could also have to do with noise in
>>>>>>>>>         the core material as I was no using an air inductor.
>>>>>>>>>
>>>>>>>>>
>>>>>>>>>         On 11/16/2018 1:19 AM, onielsen@...
>>>>>>>>>         <mailto:onielsen@...> [EVGRAY] wrote:
>>>>>>>>>>
>>>>>>>>>>         Hi Mick,
>>>>>>>>>>
>>>>>>>>>>         "If a reactive LC tank capacitor is then disconnected
>>>>>>>>>>         from the reactive source then discharged to a
>>>>>>>>>>         resistive load then reconnected energized back to the
>>>>>>>>>>         standing wave modality recharged disconnected
>>>>>>>>>>         discharged etc.  If the reactive energy is harvested
>>>>>>>>>>         in this manner are you claiming the same losses will
>>>>>>>>>>         occur as power factor correcting the reactive back
>>>>>>>>>>         into real power?"
>>>>>>>>>>
>>>>>>>>>>         Yes that's correct.
>>>>>>>>>>
>>>>>>>>>>         Common power factor correction in AC is for
>>>>>>>>>>         eliminating the reactive power that doesn't do any
>>>>>>>>>>         work but just heats the wires between the power plant
>>>>>>>>>>         and the reactive load. This is expensive for the
>>>>>>>>>>         owners of the power transmission lines and thus
>>>>>>>>>>         should be avoided. First storing the energy in a
>>>>>>>>>>         capacitor (or inductor or battery) and then dumping
>>>>>>>>>>         it to an active load will still make the power go in
>>>>>>>>>>         just one direction even though it happens in pulses.
>>>>>>>>>>         The energy is then moving from the source to the
>>>>>>>>>>         load. Reactive power has the energy moving to and
>>>>>>>>>>         from the load and power source. The power moving
>>>>>>>>>>         between the capacitor and inductor in an LC-tank is
>>>>>>>>>>         pure reactive except for the loss because of the
>>>>>>>>>>         parasitic resistance in the components and wires.
>>>>>>>>>>
>>>>>>>>>>         Regards
>>>>>>>>>>         Ole
>>>>>>>>>>
>>>>>>>>>>
>>>>>>>>>>         ---In [email protected]
>>>>>>>>>>         <mailto:[email protected]>, <mkjekyll@...>
>>>>>>>>>>         <mailto:mkjekyll@...> wrote :
>>>>>>>>>>
>>>>>>>>>>         Ole,
>>>>>>>>>>
>>>>>>>>>>         Disregarding the issue at hand with the patent
>>>>>>>>>>         terminology and not concerning ourselves with the
>>>>>>>>>>         patent just a very high Q tank.
>>>>>>>>>>
>>>>>>>>>>         If a reactive LC tank capacitor is then disconnected
>>>>>>>>>>         from the reactive source then discharged to a
>>>>>>>>>>         resistive load then reconnected energized back to the
>>>>>>>>>>         standing wave modality recharged disconnected
>>>>>>>>>>         discharged etc.  If the reactive energy is harvested
>>>>>>>>>>         in this manner are you claiming the same losses will
>>>>>>>>>>         occur as power factor correcting the reactive back
>>>>>>>>>>         into real power?
>>>>>>>>>>
>>>>>>>>>>
>>>>>>>>>>
>>>>>>>>>>         On 11/15/2018 5:36 PM, onielsen@...
>>>>>>>>>>         <mailto:onielsen@...> [EVGRAY] wrote
>>>>>>>>>>
>>>>>>>>>>>             I have only read to the following paragraph
>>>>>>>>>>>             cited below. I wonder if the applicant knows
>>>>>>>>>>>             about what he is writing.
>>>>>>>>>>>
>>>>>>>>>>>             Citing paragraph 106 of the patent application
>>>>>>>>>>>             (https://patentimages.storage.googleapis.com/53/7d/29/f7b4bd0194992d/US20070296373A1.pdf
>>>>>>>>>>>             <https://patentimages.storage.googleapis.com/53/7d/29/f7b4bd0194992d/US20070296373A1.pdf>):
>>>>>>>>>>>             "[0106] There is voltage across the inductor
>>>>>>>>>>>             connected in series to the capacitor and there
>>>>>>>>>>>             is voltage across the inductor connected in
>>>>>>>>>>>             parallel to the capacitor. Since
>>>>>>>>>>>             Power=voltage×current, a single power input
>>>>>>>>>>>             produces two branches of electromagnetic power
>>>>>>>>>>>             output, increasing the power output. In the
>>>>>>>>>>>             alternative, the present disclosure may have one
>>>>>>>>>>>             electromagnetic power output with less energy
>>>>>>>>>>>             input."
>>>>>>>>>>>
>>>>>>>>>>>
>>>>>>>>>>>
>>>>>>>>>>>             It isn't as simple as this. If using an
>>>>>>>>>>>             oscilloscope for measuring the current and
>>>>>>>>>>>             voltage it will show some phase displacement
>>>>>>>>>>>             between the current and voltage which means
>>>>>>>>>>>             reactive power. Look at the following small
>>>>>>>>>>>             videos to see how one can be misled if not
>>>>>>>>>>>             knowing how the phase between the current and
>>>>>>>>>>>             voltage is: Only the the resistive part consumes
>>>>>>>>>>>             (transforms) energy like R in figure 8.
>>>>>>>>>>>
>>>>>>>>>>>             0:42
>>>>>>>>>>>             <https://www.youtube.com/watch?v=yJEZMCCBV3U>
>>>>>>>>>>>
>>>>>>>>>>>
>>>>>>>>>>>                   Overunity Device Cop 2,5 ? explanation
>>>>>>>>>>>                   part 3.
>>>>>>>>>>>                   <https://www.youtube.com/watch?v=yJEZMCCBV3U>
>>>>>>>>>>>
>>>>>>>>>>>             9.5K views5 years ago
>>>>>>>>>>>             1:01
>>>>>>>>>>>             <https://www.youtube.com/watch?v=Jamj3-2w0eE>
>>>>>>>>>>>
>>>>>>>>>>>
>>>>>>>>>>>                   Overunity Device Cop 2,5 ? explanation
>>>>>>>>>>>                   part 2.
>>>>>>>>>>>                   <https://www.youtube.com/watch?v=Jamj3-2w0eE>
>>>>>>>>>>>
>>>>>>>>>>>             10K views5 years ago
>>>>>>>>>>
>     View attachments on the web
>     <https://groups.yahoo.com/neo/groups/EVGRAY/attachments/745755402;_ylc=X3oDMTJxbHJlNW5zBF9TAzk3MzU5NzE0BGdycElkAzI2NDM0MjMEZ3Jwc3BJZAMxNzA1MDgzNjYzBHNlYwNhdHRhY2htZW50BHNsawN2aWV3T25XZWIEc3RpbWUDMTU0MjczNTI0Ng-->
>
>     ------------------------------------------------------------------------
>     Posted by: Mick <[email protected] <mailto:[email protected]>>
>     ------------------------------------------------------------------------
>     Reply via web post
>     <https://groups.yahoo.com/neo/groups/EVGRAY/conversations/messages/109490;_ylc=X3oDMTJyZmJpcTkyBF9TAzk3MzU5NzE0BGdycElkAzI2NDM0MjMEZ3Jwc3BJZAMxNzA1MDgzNjYzBG1zZ0lkAzEwOTQ5MARzZWMDZnRyBHNsawNycGx5BHN0aW1lAzE1NDI3MzUyNDY-?act=reply&messageNum=109490>
>     	• 	Reply to sender
>     <mailto:[email protected]?subject=Re%3A%20%5BEVGRAY%5D%20Re%3A%20Neutral%20spike%20%5B1%20Attachment%5D>
>     	• 	Reply to group
>     <mailto:[email protected]?subject=Re%3A%20%5BEVGRAY%5D%20Re%3A%20Neutral%20spike%20%5B1%20Attachment%5D>
>     	• 	Start a New Topic
>     <https://groups.yahoo.com/neo/groups/EVGRAY/conversations/newtopic;_ylc=X3oDMTJlY2FybXFpBF9TAzk3MzU5NzE0BGdycElkAzI2NDM0MjMEZ3Jwc3BJZAMxNzA1MDgzNjYzBHNlYwNmdHIEc2xrA250cGMEc3RpbWUDMTU0MjczNTI0Ng-->
>     	• 	Messages in this topic
>     <https://groups.yahoo.com/neo/groups/EVGRAY/conversations/topics/109124;_ylc=X3oDMTM4aTRrcXE3BF9TAzk3MzU5NzE0BGdycElkAzI2NDM0MjMEZ3Jwc3BJZAMxNzA1MDgzNjYzBG1zZ0lkAzEwOTQ5MARzZWMDZnRyBHNsawN2dHBjBHN0aW1lAzE1NDI3MzUyNDYEdHBjSWQDMTA5MTI0>
>     (95)
>
>     ------------------------------------------------------------------------
>     Check out the automatic photo album with 2 photo(s)
>     <https://groups.yahoo.com/neo/groups/EVGRAY/photos/photomatic/532232517;_ylc=X3oDMTE4M3R1OW82BF9TAzk3MzU5NzE0BGNmOQNQSE9UT01BVElDBHNlYwNtZWdhcGhvbmU->
>     from this topic.
>     llkkefffkoiphmdd.jpg llkkefffkoiphmdd.jpg
>     <https://groups.yahoo.com/neo/groups/EVGRAY/photos/photomatic/532232517;_ylc=X3oDMTE4M3R1OW82BF9TAzk3MzU5NzE0BGNmOQNQSE9UT01BVElDBHNlYwNtZWdhcGhvbmU->
>
>     ------------------------------------------------------------------------
>     Have you tried the highest rated email app? <https://yho.com/1wwmgg>
>     With 4.5 stars in iTunes, the Yahoo Mail app is the highest rated
>     email app on the market. What are you waiting for? Now you can
>     access all your inboxes (Gmail, Outlook, AOL and more) in one
>     place. Never delete an email again with 1000GB of free cloud storage.
>     ------------------------------------------------------------------------
>
>

References

<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<CA+uJ=nf_c3JCKs1dWErvoyUkkpPE4fY7New=PtBPoMm=t6fp8Q@mail.gmail.com>

Headers

Return-Path <[email protected]>
X-Sender [email protected]
X-Apparently-To [email protected]
X-Received (qmail 25102 invoked by uid 102); 20 Nov 2018 23:03:57 -0000
X-Received from unknown (HELO mtaq5.grp.bf1.yahoo.com) (10.198.29.78) by m12.grp.bf1.yahoo.com with SMTP; 20 Nov 2018 23:03:57 -0000
X-Received (qmail 11259 invoked from network); 20 Nov 2018 23:03:56 -0000
X-Received from unknown (HELO mta4002.groups.mail.bf1.yahoo.com) (10.201.195.45) by mtaq5.grp.bf1.yahoo.com with SMTP; 20 Nov 2018 23:03:56 -0000
X-Original-Return-Path <[email protected]>
X-Received-SPF none (domain of att.net does not designate permitted sender hosts)
X-YMailISG qEY2XIAWLDvb0rIGwVnqdtXHoDOx0cSS7oIoDj7GRjS6_XZx 6txJllDWeOWGzoxvlPbZfAOzxY5lgZHJ7IzMpx5bu.Nyc.nnv1QcG__bofbC UQaNM0KUXNHbZd9hhPG70H1iql5p9NNdMHXUBMHp7Qe9KEpMgj2YJj7cwefK ojzrqxtVog35E1LotEE8xPMGBDWXxp83B37kQn7_5YvxtkGTLrlMZ_hgRGpk CWNlAhhBNFLru16iWi1U42OK0.Gag_GE5_.RxNvlxLt25zbkdwRASP7htagL lp4Mxa4Zn9ORpkGxJcf3yZmtFn13NoOKKEvqMFMv_d5uU52wnlfzIIo_x0cP XN5Gbd_AT2RGK8tr6dr.419wk2bjPSObC.vNky.TS_o7oaE8pIbwBv6U2lwk kHJ8UqRklhuq_3XeKyd45wVPoTGHWwyslcGn21EwJcsEvKxa6STvhRs5xYYE GJVjSRoUPQoo9r4i3WLuRs8BD1AVT_S07GEJpcBgYoRRecxGyX4Or24FFsE8 K.NKYOjyCeb0nfP0SDtytnLIoGOAiGRXCHmQ2OnwmkOL9XGyw5je1KXFkpGq D2kmDMF5N2e5y6Z5oTx03XhSM0WEq1e3P0HPprQWYEaHxLsSDLZjLlg57K1F AhWSejuqCqPfaLU0YCHSOgvWFH1VJFgpMRSKVRXfCnr3sGM1YqbbKCFpWpWh aW4sJ8zvFtfc_qW63LJzDWDiLXbFhWq1EXf4iH9Kvwh4iD_UIARTCP5cgzY0 V9bSzI9LZtw24sMcp5j6udXcXxGHgWPk2kVcavVaYzFWRunw0QEGVzUjkLPL YOXyCX2UZ7J7IaW9_p8_zKMyXqN6cx3s9tTCJ.F7ff4onDRe6uO1sZIxO1gE 5LzN58uXEp_MZ8erVr5LVlIzsAS.mVWVyeLc218ldaSKktUilnd8WjWfiEZQ 8jD9vX5obMBLCM8zliDmMy9PtW2qyTDrd_yYAy6m2QTIuDZtLjcuI6_lVzJA NZGTdvc6fTZdOFxj2v8PwnJ8O_Pitwo6CzLMLQvucAdgrkHPFJWbrum1XzcS KCpLcsdze8OKakmFYR2JHKxR1WrfyxM9p11epAKyfNTOrGiwyK.OqLKar3rF yV47VuJuXlBR0bwRc9.enc3AEirm7myATLxruNQqSt0MD94YEwY3MIMWW06L aqmZ9tHfoqSDeNMvnDgRCVQDp8dGvrMlVjfT_5kl1wtvOnjZhIdiFdiZKln2 fjyeVgQkvpPP3MAAOnvgvsB.pzens2NFUUi0ogzi.LtkUyHYvQb.YIFgWZRo J0nuJ5FlRzbDvW6CdwLptzQwpAgwaxvJAMY59j2sdxMWpfth5jU_rSvWtJF2 NyC_2O_i0v.JzzKUY_cVUdnf3QozMQDwKUpfqjaF8i7y2sfipN9I64qS3wpb h.vvc0zFt8VddSB8ZXcLlKZGn3vwLm7ZA_rSksKARBwUmn7ZEfVNLw--
Authentication-Results mta4002.groups.mail.bf1.yahoo.com from=att.net; domainkeys=neutral (no sig); from=att.net; dkim=pass (ok)
X-Received from 127.0.0.1 (EHLO sonic313-17.consmr.mail.bf2.yahoo.com) (74.6.133.253) by mta4002.groups.mail.bf1.yahoo.com with SMTPS; Tue, 20 Nov 2018 23:03:56 +0000
X-YMail-OSG 4v5lkS0VM1kN49cNEh.L17Pfg9qzs_nPfYnE402cIxtJfWbX6i762txakoXX9pf CoJOOv91s4W0iYVlcGqak2jtrjDeWR0mLZo7V8vGfWXJ1PR9mhl68WZbtzKRbWi74t_6tunj6XfC 5CvDtX2igXSIOQUEfbputJgNM9ufGbfHrqF7yD.4U58uwmvHcTZ473iRyADdDVi7B51mFkvv9rvX 4bnDvsTYREZoudUgKU5ypOhjsuBnLTx8D5sa5DgwfJ3KdO5Ji8ICaj845CDB0dUOQqUQw_AxBNvZ iK9xpTSKO0ne6k1xa6x___sAThqRLNlgSlMYGKPfgmHRr5DxQOuj5ahuZTmaurH1v91ldDz_UwPG 1PyVvpM8QzoyhpcTz.aJfgQTD74g9ehC2aiQYKQl7svutaAZRR1wN_jfD5CN_iGLgA6_fnCjvVib rcHZtKHu0FKgyzjip7UoQSwq0HnrqjKWQL57RBEx9zZzMe1LWTLSgHJ6WB7huO0FrXW8Ynhl3IeO CpmSSKSnDYhwQTk6O_a7Q44661Ut0cQIGFWGZz7UCxuOfM8Eso5L5v88RXNriZIb9ckqSLdshz63 WLhaNBnut29yku4o1V_4QIe7HxJGxV6Oc74yQbR85UJf.clESyzgYcTZ.Q.g6MpLdASjGAIBdb_T _yeX43KBHx467vkuCoKbS3NUobXvU5YACbRwdc7nqk9wP.ANtIurnzlbZDlCHg1o1.nM2Z67wvci ZMKN0C6ezPdyCXJSqafaiQUqAXZuix.9PNytsv5rlTApS.QeJHZiuC3Jd.dBFhthD9rDq19X57MS nZ1ePQnLXh5mKEogbzKbxPbTloSqPX1EQphy9JJsLWxbM.tnNnWjzLDbeRoOe6PB7uID1ycvlE3E DH9GZ1945aquh4K5Gatf4LbPdFk6pTkfqjz0yDeKceGr45rFP1YV_.ABX7pKNf5lH6n6ZtNIFx9s qA.XnvL9V31LzpoNvfPlZU6v.l11X6iC_LY8fjNhN97wkWdOe1cjVhrgCCGOuH8P1NVqD5Masorb OOGGX6IC2TEIUxharLwqH2nRsoAno2orxjkl1j81VkH8-
X-Received from sonic.gate.mail.ne1.yahoo.com by sonic313.consmr.mail.bf2.yahoo.com with HTTP; Tue, 20 Nov 2018 23:03:56 +0000
X-Received from ip70-189-27-193.lf.br.cox.net (EHLO [192.168.0.5]) ([70.189.27.193]) by smtp403.mail.bf1.yahoo.com (Oath Hermes SMTP Server) with ESMTPA ID 1eff894f3fef5d5e5573066dd3b5ec6a for <[email protected]>; Tue, 20 Nov 2018 23:03:54 +0000 (UTC)
To [email protected]
References <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <[email protected]> <CA+uJ=nf_c3JCKs1dWErvoyUkkpPE4fY7New=PtBPoMm=t6fp8Q@mail.gmail.com>
Message-ID <[email protected]>
Date Tue, 20 Nov 2018 17:03:55 -0600
User-Agent Mozilla/5.0 (Windows NT 10.0; WOW64; rv:60.0) Gecko/20100101 Thunderbird/60.3.0
MIME-Version 1.0
In-Reply-To <CA+uJ=nf_c3JCKs1dWErvoyUkkpPE4fY7New=PtBPoMm=t6fp8Q@mail.gmail.com>
Content-Type multipart/alternative; boundary="------------7E6E33048140D37030D338FD"
Content-Language en-US
X-Originating-IP 10.201.195.45
Subject Re: [EVGRAY] Re: Neutral spike
X-Yahoo-Group-Post member; u=554418533; y=EquuheNZ1WekBW66sQRudOs0opARcnBsQkhMsaZPcFiDFXCeM76jN9pj
X-Yahoo-Profile [email protected]
From Norman Wootan <[email protected]>