Hi Sven,

"If I switch 2x 230V / 24V transformers primarily in parallel I reduce the impedance since the energy is distributed to both transformers."
No this doesn't change the impedance. If the primaries are put in parallel and the secondaries are put in series (and in phase) this transforms the impedance to another ratio that delivers the same power to a load having four times the impedance of a load with only one transformer. The output voltage is doubled to 48V and thus the current must be halved for the same output power which quadruples the load impedance.

A switched mode converter can also transform the voltage but a transformer is a simple way of doing that. The transformer just has a fixed ration between the input and output sides. Transformers come in many different ratios and can be custom made for the required ratio.

"I also wonder if I should twist the lines back and forth all together."
This is a must when the frequency is increased and the wires else becomes a coil with one turn and thus stores the current as a magnetic field going through the formed loop. When the wires are twisted they become more like a transmission line that doesn't store the energy but transfers it to some other place.

Regards
Ole

 

---In [email protected], <s.friedrich@...> wrote :

 Hi Ole,
 
 with a load resistor I waste the energy yes, I would like to push this into the battery.
 
 If I switch 2x 230V / 24V transformers primarily in parallel I reduce the impedance since the energy is distributed to both transformers.
 
 You mean to cache the energy after the push-pull transformer and then discharge it. Help that gets more and more complicated.
 
 There are also people who have loaded the capacitors directly into the battery, apparently the lead-acid batteries keep that out. They are only sharp pulses. It would be nice if you could install a kind of electrical sink, so that the energy of the transformer falls almost without resistance, perhaps with large capacitors and then discharged in the battery with a separate circuit or the capacitors swallow the energy peaks and give them with lower voltage from.
 
 I'm a bit overwhelmed, and working on a new constellation with shorter and equal connections between the diodes. I also wonder if I should twist the lines back and forth all together.
 
 regards
 
 Sven   Gesendet: Samstag, 03. März 2018 um 19:57 Uhr
 Von: "onielsen@... [EVGRAY]" <[email protected]>
 An: [email protected]
 Betreff: Re: AW: Re: AW: Re: Aw: Re: Re: Re: Re: AW: [EVGRAY] Re: "Impressive"!
   Hi Sven,
 
 For transformation between output to load impedance the ratio of the transformer has to fit the impedance ratio to be able to do its job. Else the output voltage and impedance must be chosen to fit the load voltage and impedance or vice versa.
 
 Or the load has to be disconnected from the capacitors even when the capacitors haven't fully discharged which gives the problem of switching off the SCRs. A load that can absorb the energy before the next charging cycle requires the proper resistance for the capacitance value chosen. This resistance can be calculated when the other parameters of the circuit are known. The other circuit parameters can also be calculated for a given load and worked backwards if the load is known as everything affects each other.
 
 "I have already considered whether to connect the secondary coil of the push-pull transformer with a FWBR and conducts the energy in a mains choke and then connect in the battery with flyback diode as a step-down converter with only 50 Hz or 2x 230V / 24V transformers in parallel to the secondary winding to lower the impedance."
 
 Or use a power resistor to dissipate the excess power as heat. This can transfer the energy of the capacitors into heat at almost any rate when correct chosen. The series inductance will be what limits the current and thus must be small enough to be able to discharge the capacitors fast enough to turn off the SCRs before the next capacitor charging. This power resistor can be added in parallel to make the load impedance less or in series to make it greater.
 
 Regards
 Ole
 
 
 ---In [email protected], <s.friedrich@...> wrote :
   Hi Ole,
 
 you just have to create a low impedance at the push-pull transformer. The problem is that this transformer is just a isolating transformer so the voltage is not down-converted to 24 volts.
 
 The 230/24 volt transformers I have to connect to the secondary side of the pushpull generates a higher impedance which ensures longer switching times at the SCR.
 
 I have already considered whether to connect the secondary coil of the push-pull transformer with a FWBR and conducts the energy in a mains choke and then connect in the battery with flyback diode as a step-down converter with only 50 Hz or 2x 230V / 24V transformers in parallel to the secondary winding to lower the impedance.
 
 The only question is when the 24V winding is connected with a FWBR to the battery, the battery will act against it with its own voltage and create additional impedance in the push-pull transformer.
 
 The easiest way would be to connect the secondary winding directly to the battery and to charge it with the energy peaks.
 
 I'm just not comfortable because the batteries are in excellent condition and I do not want to destroy them.
 
 regards
 
 Sven

References

<[email protected]>
<[email protected]>
<[email protected]>
<[email protected]>
<trinity-565234d7-b821-4b46-bd38-c113c20da8a6-1520105098226@3c-app-gmx-bs63>

Headers

Return-Path <[email protected]>
X-Sender [email protected]
X-Apparently-To [email protected]
X-Received (qmail 30857 invoked by uid 102); 3 Mar 2018 21:30:05 -0000
X-Received from unknown (HELO mtaq2.grp.bf1.yahoo.com) (10.193.84.33) by m9.grp.bf1.yahoo.com with SMTP; 3 Mar 2018 21:30:05 -0000
X-Received (qmail 13196 invoked from network); 3 Mar 2018 21:30:05 -0000
X-Received from unknown (HELO mta1005.groups.mail.bf1.yahoo.com) (98.139.245.164) by mtaq2.grp.bf1.yahoo.com with SMTP; 3 Mar 2018 21:30:05 -0000
X-Original-Return-Path <[email protected]>
X-Received-SPF pass (domain of yahoogroups.com designates 74.6.133.92 as permitted sender)
X-YMailISG quf2j0QWLDtuEyNHbiA2I6eiGzWmJRW87pM13nhpesR9P_A0 5sQhCZpqh9.6pkbG3KnvdCwKU6rA1ljDDOqbtKf1CGZF.SkJ9SnJJB77lT6h 51X5SBYL_qui.Jk644ENRbCsQNTO1UMKe3NgXV3fgWVIMjz7xLClSzpxqhJy mVyJ123H1x.arW3o59aCluIiTGyt5w6JxitfnfC48ylfk7RZB2S2vSyECrHQ s3hQwCRrQYjOOsKE54qC4zfVZ6fg5fsT390.MKusefu0C.dEYOde6fpjPUAQ yiBWpVoVJYYFPrsmfGF3FqTRzhCnUZAxCkJoXDDB.W.OSPjl4yyQgSLUt_Uf xb.th4_rleRWs0W0v7chouv027FWkEQ02OUW6YOdATKzPMeah1o4cNDQQr4D HU53yj.FiiH2e5ECRGTIlL9GwQCYYTdT.jG13I8SOKgBZ9ZOzjZvfa77jd1V 5CcUV9iRTqgQ_L3.qVd3iym4ppGTXy4gyqvqTfeXPFnYzKgHtj4no9QVjSvi EteCS_Q1_XZmgB5ziEISB_yxN2i_5UhiCqaKI7F2fo2Rhbk2Y4HbbycXqhUf 7.IIolEOA6kmGW_qn6CSdrRLJWyg3ftRtz8HBCZbHs7WuxR0uOtEBagoLr.V BS9uuT1Qbb6ga2.Vsqx1X5oxl6yd579roGrXO05DuEioIgUm0LVirp97pGnA RKExIFeugZ8P2cnBSzrkkUBmH7_z4NdLXCfbeOASw9wzcRNDwN9CGujY__wx FZwC5Pzql5THTE3lqPttVrWY3Li4H0vkrgDA_cdD8AqllTpiH7CB_ztoVBYH cciIElOeRpJR_QTPNs3xR5BkWjtgPQkK6j2DTylR5wMxgwfV8um6jKRvKc1L izoThLEC0FJmt_3E3ccDHgxSB.BY6JtGwW7L_Smjsn6XI5LOPLJgjtoB7LHY YIK9v3VKxiVGq8CryulJpNjJ1g6wFXyy_sUqQghX8r94k4Xxeh4d8jrNHvxL 4Ik5ybV0B3psXo0PXqbY265HWWhZjWEh9WzROwDLYg1eSXy.1If28sINK997 _nU0Wxs6G0L7gv0EaJrjA9bS90aiinRiObbJyKL54Yb0OnaMW6hCvICPx05c t2pouS55h8usNVZatTKi9nXgxYWIvMEvGZ7z2DV1VU2O8LcUQ_jRnDBjG_NF EEEBE6VkptNONDTCQ21XK5fB4o_xThW1f0A-
Authentication-Results mta1005.groups.mail.bf1.yahoo.com from=yahoogroups.com; domainkeys=neutral (no sig); from=yahoogroups.com; dkim=permerror (bad sig)
X-Received from 127.0.0.1 (EHLO sonic321-37.consmr.mail.bf2.yahoo.com) (74.6.133.92) by mta1005.groups.mail.bf1.yahoo.com with SMTPS; Sat, 03 Mar 2018 21:30:05 +0000
X-Received from sonic.gate.mail.ne1.yahoo.com by sonic321.consmr.mail.bf2.yahoo.com with HTTP; Sat, 3 Mar 2018 21:30:05 +0000
Date Sat, 03 Mar 2018 21:30:04 +0000
X-Received from [127.0.0.1] by gapi7.grp.bf1.yahoo.com with NNFMP; 03 Mar 2018 21:30:04 -0000
To [email protected]
X-Original-Return-Path [email protected]
X-Original-From [email protected]
X-Mailer Yahoo Groups Message Poster
References <[email protected]> <[email protected]> <[email protected]> <[email protected]> <trinity-565234d7-b821-4b46-bd38-c113c20da8a6-1520105098226@3c-app-gmx-bs63>
X-Yahoo-Newman-Property groups-compose
Message-ID <[email protected]>
In-Reply-To <trinity-565234d7-b821-4b46-bd38-c113c20da8a6-1520105098226@3c-app-gmx-bs63>
MIME-Version 1.0
Content-Type multipart/alternative; boundary="9nlWnTS9ocNmxdhsK3FKVLWiM6a5jwOaA8HvrLV"
X-Originating-IP 85.81.0.233
X-Yahoo-Post-IP 85.81.0.233
Reply-To [email protected]
Subject Re: Aw: Re: AW: Re: AW: Re: Re: Re: Re: Re: AW: [EVGRAY] Re: "Impressive"!
X-Yahoo-Group-Post member; u=115023864; y=7WRTNF97L9tnPZ33RSmLif-Ywd5qNi1iqp22HdAlgW4fS0EJLwTQ
X-Yahoo-Profile onielsen2000
From [email protected]